Ground-truth scope and provenance
The loop: who, what, when, where and why
Understand the process model
Observe a condition. Understand the decision.
No regulatory PID loop is defined here. Use this normalized synthetic trend to learn threshold crossing and dwell time.
A threshold breach must persist for the full dwell before indication turns on. It resets when the signal falls below threshold. This simple teaching logic does not model latching, voting, an SIS or a field-approved alarm basis.
Make a change. See its effect.
Understand the selected method
Virtual relay experiment · evidence for Ku and Pu
Oscillate the known model with a bounded relay, measure the cycle, then apply an ultimate-gain recipe. The relay is a test method; ZN and Tyreus–Luyben are the recipes that use its evidence.
No relay evidence yet.
As-found
BaselineThe library’s starting controller. Edit it to reproduce a tuning problem.
As-left
Your candidateChoose a compatible recipe, or edit P, I and D directly.
Why this candidate works on this model
One process. Two controllers.
Compare all compatible tuning methods on this exact test
Same model, setpoint, load and output bounds. Response-time recipes use their balanced starting targets; ZN uses your selected controller. A relay-based row requires the virtual relay above. A low IAE alone does not establish the best tune.
The model is known. Is the test good enough?
Learn to explain the tune.
Try this exercise
- Read the loop role, model, known parameters and source-test verdict.
- Choose a compatible tuning method. Read its formula and compare speed, overshoot, error and output movement.
- Increase Kc by 50%. Then halve Ti. Change one setting at a time.
- Add a load disturbance. Does a faster response require more actuator work?
- Explain your choice, save the exercise, or download the report.
What the controls mean
- Kc · proportional gain
- Higher magnitude reacts harder to error. Its sign must agree with Kp for negative feedback here.
- Ti · integral time
- Smaller positive Ti removes sustained error faster, with greater oscillation risk. Zero turns integral off.
- Td · derivative time
- Anticipates PV movement using a filtered derivative. The filter N is 10; derivative acts on PV to avoid setpoint kick.
Process models and all tuning methods · reference guide
Control structures: how loop architecture changes tuning
These are LoopIQ architecture lessons. The response comparison above isolates one regulatory model; it does not simulate these full control structures. Use the guide to understand what must be tuned and verified separately.
Practice with a purpose
Predict, change one variable, observe PV and OP, then defend your decision. Use the manual for worksheets and repeat the same test to measure learning over time.
↓ Printable practice manualReason through the evidence
Answer these three questions, then review the explanation. Your recorded quiz score measures these questions; it does not certify field competence.
Quick check
Your practice record
Record a run after answering the quiz and explaining the evidence. Attempts stay on this device; download your history to keep a copy. Compare performance only when the process, baseline and test conditions match.